Honeywell 05701-A-0301 | Single Channel Control Card

  • Model: 05701-A-0301
  • Brand: Honeywell (Zellweger Sieger)
  • Series: 5701 Control System
  • Core Function: Provides control, display, and alarm facilities for connected gas detectors.
  • Type: Single Channel Control Card (4-20mA)
  • Key Specs: 4-20mA Input, Microprocessor Controlled, LED Alarms
Category:
Phone: +86 15383419322
WhatsApp: +86 15383419322
WhatsApp QR Code
Brand:

Description

Key Technical Specifications

  • Input Signal: 4-20mA Analog
  • Display: 4-part LCD (25-segment analog, 4-char digital)
  • Alarm Indicators: A1, A2, A3 LEDs (Gas), Fault, Inhibit
  • User Interface: Push-button (Reset Alarm / Card Select)
  • Alarm Resolution: 1% FSD step
  • Power Supply: 18V to 32V DC
  • Power Consumption: 3.25W (Typical)
  • Configuration Storage: EEPROM
  • Dimensions: 17 cm x 2.5 cm x 11.2 cm
  • Weight: 0.165 kg
  • Electronic Drift: <2% / 6 months
  • Optional Add-on: Plug-in Analogue Output Module

Product Introduction

You’re walking through a petrochemical plant and a gas monitor starts screaming. The 05701-A-0301 is the brain sitting behind that front panel display. It takes the raw 4-20mA signal from your gas detector and translates it into readable numbers, alarm states, and relay actions. No card, no visibility. No visibility, no safety.

This specific variant is strictly for 4-20mA transmitters. It runs on 18-32V DC and sips only 3.25W. The microprocessor handles all the logic, storing your config in EEPROM so you don’t lose settings during a power blip. Honestly, if your gas readings are drifting or the A1/A2/A3 LEDs are stuck, this card is usually the culprit—not the sensor.

 

Troubleshooting Quick Reference

  • Blank Display | Power Loss | High (80%) | Measure DC voltage at card terminals | Verify 18-32V DC supply; check backplane seating
  • No Gas Reading | Sensor/Loop Open | High (70%) | Measure loop current at card input | Check 4-20mA wiring; verify sensor is powered
  • False Alarms | EEPROM Corruption | Medium (50%) | Re-download config via Engineering Card | Power cycle; reconfigure alarm setpoints
  • LED Stuck On | Latch Fault | Medium (40%) | Press RESET/SELECT button | If persists, card logic failure—replace
  • Drifting Readings | Card Aging | Low (30%) | Compare with calibrated test gas | If sensor tests good, card drift >2%/6mo—replace
Honeywell 05701-A-0301

Honeywell 05701-A-0301

Application Scenarios & Pain Points

  • Offshore Gas Detection: Salt spray and vibration. Standard controllers corrode at the terminals. This card’s sealed design and solid-state construction handle the marine environment.
  • Confined Space Monitoring: Requires fast alarm response. The 1% FSD resolution means you catch leaks before they hit LEL thresholds. Slower cards miss the window.
  • Remote Unmanned Sites: Power fluctuations are common. The 18-32V DC wide input range keeps the card alive when battery banks sag during generator switchover.

 

Compatible Replacement Models

  • Drop-in Replacement: 05701-A-0301 (Exact match. 4-20mA variant. No config change if using same detector type.)
  • ⚠️ Hardware Variant: 05701-A-0302 (Catalytic sensor version. Different internal drive module. NOT interchangeable with 4-20mA sensors.)
  • Hardware Incompatible: 05704-A-0144 (Four-channel gas control card. Different form factor, pinout, and rack slot. Do not attempt to fit.)