Honeywell CC-TDIL01 | 32-Ch 24V DC DI IOTA, Non-Redundant

  • Model: CC-TDIL01 (PWA, DI 24V IOTA 32 24V, non-redundant)
  • Brand: Honeywell
  • Series: Experion PKS / Experion LX C-Series I/O
  • Core Function: Terminates and conditions 32 channels of 24 V DC digital input signals for the paired CC-PDIL01 DI module.
  • Type: Digital Input IOTA (terminal board)
  • Key Specs: 32 DI channels; 24 V DC; non-redundant; mates with CC-PDIL01; ~4.2 W module power; 2,500 V isolation rating.
Category:
Phone: +86 15383419322
WhatsApp: +86 15383419322
WhatsApp QR Code
Brand:

Description

Key Technical Specifications

Parameter Value
Product type Digital Input IOTA (terminal board)
Platform Honeywell Experion C-Series / C300 I/O
Channels 32 digital inputs
Signal level 24 V DC
Redundancy Non-redundant
Typical mating module CC-PDIL01 32-ch 24 V DC DI module
Redundant alternative CC-TDIL11
Typical module power ~4.2 W
Typical module current ~0.19 A
Typical per-channel power ~0.132 W
Isolation rating 2,500 V
Operating temperature -40 °C to +70 °C
Humidity 5–95% non-condensing
Standards reference DIN 3204

 

Product Introduction

Replacing a DI IOTA looks simple until you discover the field wiring is tied to a specific terminal layout. The CC-TDIL01 sits at that junction. It is the non-redundant 32-channel 24 V DC digital input terminal board for Honeywell C-Series I/O, and it carries the field wiring while the CC-PDIL01 module handles logic-side processing.

This board is useful when you need a clean, documented replacement for an existing non-redundant DI point group. With 32 channels, ~4.2 W module power, and a 2,500 V isolation rating, it fits typical discrete status monitoring duties such as valve position switches, relay contacts, and permissive signals. It is not a redundant IOTA. If the loop requires dual-path availability, CC-TDIL11 is the correct counterpart.

QA/QC Transparency SOP

  1. Intake & Origin Verification: Confirm model CC-TDIL01, Honeywell part reference if present, revision, and serial number. Inspect for bent pins, cracked terminal blocks, corrosion, or heat discoloration.
  2. Live Functional Testing: Mount the IOTA on a compatible C-Series test rack. Install a known-good CC-PDIL01 module. Apply 24 V DC and verify LED indicators, terminal continuity, and module communication.
  3. Electrical Parameter Tests: Measure 24 V DC supply current and compare against the ~0.19 A / ~4.2 W reference. Check terminal-to-terminal continuity and isolation paths with a multimeter. Reject boards with shorted rails or damaged insulation.
  4. Firmware/Config Verification: Read module identity and diagnostic status from the paired CC-PDIL01. The IOTA itself does not carry user firmware, but the mating module revision must match the cabinet design.
  5. Final QC & Anti-Static Packaging: Record test results, photograph the nameplate and terminals, and pack in ESD-safe material with terminal protection caps.

 

Field Engineer Gotchas

  • Wrong IOTA revision: CC-TDIL01 is non-redundant. Installing it where CC-TDIL11 was specified removes redundancy. Check the cabinet drawing first.
  • Module mismatch: CC-TDIL01 pairs with CC-PDIL01. It does not replace DO, AI, AO, or SOE IOTAs. Forcing the wrong module will not fix a channel fault.
  • Terminal block damage: The two-level removable terminals are the most common failure point. A cracked terminal block can cause intermittent channel readings even if the module is healthy.
  • Field power wiring errors: The IOTA routes 24 V DC field power. Reversed polarity or a shared ground mistake can knock out an entire channel group. Verify field supply before energizing.
  • Assuming isolation fixes ground loops: The 2,500 V isolation rating is not a blanket cure for poor grounding. If multiple cabinets share inconsistent 24 V DC references, you will still see noise or false trips.
Honeywell CC-TDIL01

Honeywell CC-TDIL01

Application Scenarios

  • Refinery pump permissive monitoring: Collects suction pressure switch, discharge valve position, and seal failure signals for C300 interlocks.
  • Chemical batch reactor: Reads agitator running, jacket valve open, and door interlock status during recipe execution.
  • Power plant auxiliary systems: Monitors lube oil pressure switches, cooling fan status, and breaker auxiliary contacts.
  • Water treatment plant: Accepts level switch, pump run feedback, and valve limit switch signals from remote MCCs.

 

FAQ

Is CC-TDIL01 the DI module itself?
No. It is the IOTA terminal board. The DI module is typically CC-.

No. Use CC-TDIL11 for redundant 32-ch 24 V DC digital input.

What module plugs into it?
CC- 32-ch 24 V DC digital input module.

Does it support HART or analog signals?
No. It is for 24 V DC discrete inputs only.

What is its power draw?
Approximately 4.2 W / 0.19 A for the module assembly, with about 0.132 W per channel.

Is it hot-swappable?
C-Series I/O supports modular replacement, but any live work must follow site procedures, OEM guidance, and loop impact checks.

How do I confirm compatibility before buying?
Check the cabinet BOM, IOTA position, mating CC- module, revision, and terminal block condition. Match them to the installed configuration.